説明はトップページにあります。

nut top

     スタンドアローン

ホスト(サーバー)とUPS1200LXはUSBケーブルで接続。
centos6.4ではEPELリポジトリーを導入後下記コマンドでNUT2.6.5-2がインストールされます。
yum install nut nut-client nut-cgi

インストール後下記コンフィギュレーションファイルを変更して下さい。


下記ファイルは変更不要。
/lib/udev/rules.d/62-nut-usbups.rules


下記ファイルは変更不要。
/etc/ups/hosts.conf


下記ファイルに追加することにより、Network UPS Toolが自動起動します。
/etc/rc.d/rc.local

#!/bin/sh
#
# This script will be executed *after* all the other init scripts.
# You can put your own initialization stuff in here if you don't
# want to do the full Sys V style init stuff.

touch /var/lock/subsys/local
/sbin/blazer_usb -a ups <-------------------------------------------この行追加
/sbin/upsdrvctl start <---------------------------------------------この行追加
/usr/sbin/upsd <--------------------------------------------------この行追加
/usr/sbin/upsmon <------------------------------------------------この行追加



下記ファイルの変更。
/etc/ups/nut.conf

# Network UPS Tools: example nut.conf
#
##############################################################################
# General section
##############################################################################
# The MODE determines which part of the NUT is to be started, and which
# configuration files must be modified.
#
# This file try to standardize the various files being found in the field, like
# /etc/default/nut on Debian based systems, /etc/sysconfig/ups on RedHat based
# systems, ... Distribution's init script should source this file to see which
# component(s) has to be started.
#
# The values of MODE can be:
# - none: NUT is not configured, or use the Integrated Power Management, or use
# some external system to startup NUT components. So nothing is to be started.
# - standalone: This mode address a local only configuration, with 1 UPS
# protecting the local system. This implies to start the 3 NUT layers (driver,
# upsd and upsmon) and the matching configuration files. This mode can also
# address UPS redundancy.
# - netserver: same as for the standalone configuration, but also need
# some more network access controls (firewall, tcp-wrappers) and possibly a
# specific LISTEN directive in upsd.conf.
# Since this MODE is opened to the network, a special care should be applied
# to security concerns.
# - netclient: this mode only requires upsmon.
#
# IMPORTANT NOTE:
# This file is intended to be sourced by shell scripts.
# You MUST NOT use spaces around the equal sign!

MODE=standalone <-------------------------------------------------この行変更



下記ファイルの変更。
/etc/ups/ups.conf

# Network UPS Tools: example ups.conf
#
# --- SECURITY NOTE ---
#
# If you use snmp-ups and set a community string in here, you
# will have to secure this file to keep other users from obtaining
# that string. It needs to be readable by upsdrvctl and any drivers,
# and by upsd.
#
# ---
#
# This is where you configure all the UPSes that this system will be
# monitoring directly. These are usually attached to serial ports, but
# USB devices and SNMP devices are also supported.
#
# This file is used by upsdrvctl to start and stop your driver(s), and
# is also used by upsd to determine which drivers to monitor. The
# drivers themselves also read this file for configuration directives.
#
# The general form is:
#
# [upsname]
# driver = <drivername>
# port = <portname>
# < any other directives here >
#
# The section header ([upsname]) can be just about anything as long as
# it is a single word inside brackets. upsd uses this to uniquely
# identify a UPS on this system.
#
# If you have a UPS called snoopy, your section header would be "[snoopy]".
# On a system called "doghouse", the line in your upsmon.conf to monitor
# it would look something like this:
#
# MONITOR snoopy@doghouse 1 upsmonuser mypassword master
#
# It might look like this if monitoring in slave mode:
#
# MONITOR snoopy@doghouse 1 upsmonuser mypassword slave
#
# Configuration directives
# ------------------------
#
# These directives are common to all drivers that support ups.conf:
#
# driver: REQUIRED. Specify the program to run to talk to this UPS.
# apcsmart, bestups, and sec are some examples.
#
# port: REQUIRED. The serial port where your UPS is connected.
# /dev/ttyS0 is usually the first port on Linux boxes, for example.
#
# sdorder: optional. When you have multiple UPSes on your system, you
# usually need to turn them off in a certain order. upsdrvctl
# shuts down all the 0s, then the 1s, 2s, and so on. To exclude
# a UPS from the shutdown sequence, set this to -1.
#
# The default value for this parameter is 0.
#
# nolock: optional, and not recommended for use in this file.
#
# If you put nolock in here, the driver will not lock the
# serial port every time it starts. This may allow other
# processes to seize the port if you start more than one by
# mistake.
#
# This is only intended to be used on systems where locking
# absolutely must be disabled for the software to work.
#
# maxstartdelay: optional. This can be set as a global variable
# above your first UPS definition and it can also be
# set in a UPS section. This value controls how long
# upsdrvctl will wait for the driver to finish starting.
# This keeps your system from getting stuck due to a
# broken driver or UPS.
#
# The default is 45 seconds.
#
#
# Anything else is passed through to the hardware-specific part of
# the driver.
#
# Examples
# --------
#
# A simple example for a UPS called "powerpal" that uses the blazer_ser
# driver on /dev/ttyS0 is:
#
# [powerpal]
# driver = blazer_ser
# port = /dev/ttyS0
# desc = "Web server"
#
# If your UPS driver requires additional settings, you can specify them
# here. For example, if it supports a setting of "1234" for the
# variable "cable", it would look like this:
#
# [myups]
# driver = mydriver
# port = /dev/ttyS1
# cable = 1234
# desc = "Something descriptive"
#
# To find out if your driver supports any extra settings, start it with
# the -h option and/or read the driver's documentation.
[ups] <-----------------------------------------------------------この行追加
driver = blazer_usb <-----------------------------------------------この行追加
port = auto <-----------------------------------------------------この行追加
vendorid = 0001 <--------------------------------------------------この行追加
productid = 0000 <-------------------------------------------------この行追加
subdriver = krauler <-----------------------------------------------この行追加
desc = "Soundhouse UPS 1200LX" <---------------------------------この行追加



下記ファイルは変更不要。
/etc/ups/upsd.conf


下記ファイルの変更。
/etc/ups/upsd.users

# Network UPS Tools: Example upsd.users
#
# This file sets the permissions for upsd - the UPS network daemon.
# Users are defined here, are given passwords, and their privileges are
# controlled here too. Since this file will contain passwords, keep it
# secure, with only enough permissions for upsd to read it.

# --------------------------------------------------------------------------

# Each user gets a section. To start a section, put the username in
# brackets on a line by itself. To set something for that user, specify
# it under that section heading. The username is case-sensitive, so
# admin and AdMiN are two different users.
#
# Possible settings:
#
# password: The user's password. This is case-sensitive.
#
# --------------------------------------------------------------------------
#
# actions: Let the user do certain things with upsd.
#
# Valid actions are:
#
# SET - change the value of certain variables in the UPS
# FSD - set the "forced shutdown" flag in the UPS
#
# --------------------------------------------------------------------------
#
# instcmds: Let the user initiate specific instant commands. Use "ALL"
# to grant all commands automatically. There are many possible
# commands, so use 'upscmd -l' to see what your hardware supports. Here
# are a few examples:
#
# test.panel.start - Start a front panel test
# test.battery.start - Start battery test
# test.battery.stop - Stop battery test
# calibrate.start - Start calibration
# calibrate.stop - Stop calibration
#
# --------------------------------------------------------------------------
#
# Example:
#
# [admin]
# password = mypass
# actions = SET
# instcmds = ALL
#

#
# --- Configuring for a user who can execute tests only
#
# [testuser]
# password = pass
# instcmds = test.battery.start
# instcmds = test.battery.stop

#
# --- Configuring for upsmon
#
# To add a user for your upsmon, use this example:
#
# [upsmon]
# password = pass
# upsmon master
# or
# upsmon slave
#
# The matching MONITOR line in your upsmon.conf would look like this:
#
# MONITOR myups@localhost 1 upsmon pass master (or slave)
[upsmon] <-------------------------------------------------------この行追加
password = password <---------------------------------------------この行追加
upsmon master <--------------------------------------------------この行追加




下記ファイルの変更。
/etc/ups/upsmon.conf

# Network UPS Tools: example upsmon configuration
#
# This file contains passwords, so keep it secure.

# --------------------------------------------------------------------------
# RUN_AS_USER <userid>
#
# By default, upsmon splits into two processes. One stays as root and
# waits to run the SHUTDOWNCMD. The other one switches to another userid
# and does everything else.
#
# The default nonprivileged user is set at compile-time with
# 'configure --with-user=...'.
#
# You can override it with '-u <user>' when starting upsmon, or just
# define it here for convenience.
#
# Note: if you plan to use the reload feature, this file (upsmon.conf)
# must be readable by this user! Since it contains passwords, DO NOT
# make it world-readable. Also, do not make it writable by the upsmon
# user, since it creates an opportunity for an attack by changing the
# SHUTDOWNCMD to something malicious.
#
# For best results, you should create a new normal user like "nutmon",
# and make it a member of a "nut" group or similar. Then specify it
# here and grant read access to the upsmon.conf for that group.
#
# This user should not have write access to upsmon.conf.
#
# RUN_AS_USER nutmon

# --------------------------------------------------------------------------
# MONITOR <system> <powervalue> <username> <password> ("master"|"slave")
#
# List systems you want to monitor. Not all of these may supply power
# to the system running upsmon, but if you want to watch it, it has to
# be in this section.
#
# You must have at least one of these declared.
#
# <system> is a UPS identifier in the form <upsname>@<hostname>[:<port>]
# like ups@localhost, su700@mybox, etc.
#
# Examples:
#
# - "su700@mybox" means a UPS called "su700" on a system called "mybox"
#
# - "fenton@bigbox:5678" is a UPS called "fenton" on a system called
# "bigbox" which runs upsd on port "5678".
#
# The UPS names like "su700" and "fenton" are set in your ups.conf
# in [brackets] which identify a section for a particular driver.
#
# If the ups.conf on host "doghouse" has a section called "snoopy", the
# identifier for it would be "snoopy@doghouse".
#
# <powervalue> is an integer - the number of power supplies that this UPS
# feeds on this system. Most computers only have one power supply, so this
# is normally set to 1. You need a pretty big or special box to have any
# other value here.
#
# You can also set this to 0 for a system that doesn't supply any power,
# but you still want to monitor. Use this when you want to hear about
# changes for a given UPS without shutting down when it goes critical,
# unless <powervalue> is 0.
#
# <username> and <password> must match an entry in that system's
# upsd.users. If your username is "monmaster" and your password is
# "blah", the upsd.users would look like this:
#
# [monmaster]
# password = blah
# upsmon master (or slave)
#
# "master" means this system will shutdown last, allowing the slaves
# time to shutdown first.
#
# "slave" means this system shuts down immediately when power goes critical.
#
# Examples:
#
# MONITOR myups@bigserver 1 monmaster blah master
# MONITOR su700@server.example.com 1 upsmon secretpass slave
# MONITOR myups@localhost 1 upsmon pass master (or slave)
MONITOR ups@localhost 1 upsmon password master <-------------------------この行追加

# --------------------------------------------------------------------------
# MINSUPPLIES <num>
#
# Give the number of power supplies that must be receiving power to keep
# this system running. Most systems have one power supply, so you would
# put "1" in this field.
#
# Large/expensive server type systems usually have more, and can run with
# a few missing. The HP NetServer LH4 can run with 2 out of 4, for example,
# so you'd set that to 2. The idea is to keep the box running as long
# as possible, right?
#
# Obviously you have to put the redundant supplies on different UPS circuits
# for this to make sense! See big-servers.txt in the docs subdirectory
# for more information and ideas on how to use this feature.

MINSUPPLIES 1

# --------------------------------------------------------------------------
# SHUTDOWNCMD "<command>"
#
# upsmon runs this command when the system needs to be brought down.
#
# This should work just about everywhere ... if it doesn't, well, change it.

SHUTDOWNCMD "/sbin/shutdown -h +0"

# --------------------------------------------------------------------------
# NOTIFYCMD <command>
#
# upsmon calls this to send messages when things happen
#
# This command is called with the full text of the message as one argument.
# The environment string NOTIFYTYPE will contain the type string of
# whatever caused this event to happen.
#
# Note that this is only called for NOTIFY events that have EXEC set with
# NOTIFYFLAG. See NOTIFYFLAG below for more details.
#
# Making this some sort of shell script might not be a bad idea. For more
# information and ideas, see pager.txt in the docs directory.
#
# Example:
# NOTIFYCMD /usr/local/ups/bin/notifyme

# --------------------------------------------------------------------------
# POLLFREQ <n>
#
# Polling frequency for normal activities, measured in seconds.
#
# Adjust this to keep upsmon from flooding your network, but don't make
# it too high or it may miss certain short-lived power events.

POLLFREQ 5

# --------------------------------------------------------------------------
# POLLFREQALERT <n>
#
# Polling frequency in seconds while UPS on battery.
#
# You can make this number lower than POLLFREQ, which will make updates
# faster when any UPS is running on battery. This is a good way to tune
# network load if you have a lot of these things running.
#
# The default is 5 seconds for both this and POLLFREQ.

POLLFREQALERT 5

# --------------------------------------------------------------------------
# HOSTSYNC - How long upsmon will wait before giving up on another upsmon
#
# The master upsmon process uses this number when waiting for slaves to
# disconnect once it has set the forced shutdown (FSD) flag. If they
# don't disconnect after this many seconds, it goes on without them.
#
# Similarly, upsmon slave processes wait up to this interval for the
# master upsmon to set FSD when a UPS they are monitoring goes critical -
# that is, on battery and low battery. If the master doesn't do its job,
# the slaves will shut down anyway to avoid damage to the file systems.
#
# This "wait for FSD" is done to avoid races where the status changes
# to critical and back between polls by the master.

HOSTSYNC 15

# --------------------------------------------------------------------------
# DEADTIME - Interval to wait before declaring a stale ups "dead"
#
# upsmon requires a UPS to provide status information every few seconds
# (see POLLFREQ and POLLFREQALERT) to keep things updated. If the status
# fetch fails, the UPS is marked stale. If it stays stale for more than
# DEADTIME seconds, the UPS is marked dead.
#
# A dead UPS that was last known to be on battery is assumed to have gone
# to a low battery condition. This may force a shutdown if it is providing
# a critical amount of power to your system.
#
# Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT.
# Otherwise you'll have "dead" UPSes simply because upsmon isn't polling
# them quickly enough. Rule of thumb: take the larger of the two
# POLLFREQ values, and multiply by 3.

DEADTIME 15

# --------------------------------------------------------------------------
# POWERDOWNFLAG - Flag file for forcing UPS shutdown on the master system
#
# upsmon will create a file with this name in master mode when it's time
# to shut down the load. You should check for this file's existence in
# your shutdown scripts and run 'upsdrvctl shutdown' if it exists.
#
# See the shutdown.txt file in the docs subdirectory for more information.

POWERDOWNFLAG /etc/killpower

# --------------------------------------------------------------------------
# NOTIFYMSG - change messages sent by upsmon when certain events occur
#
# You can change the default messages to something else if you like.
#
# NOTIFYMSG <notify type> "message"
#
# NOTIFYMSG ONLINE "UPS %s on line power"
# NOTIFYMSG ONBATT "UPS %s on battery"
# NOTIFYMSG LOWBATT "UPS %s battery is low"
# NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
# NOTIFYMSG COMMOK "Communications with UPS %s established"
# NOTIFYMSG COMMBAD "Communications with UPS %s lost"
# NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"
# NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"
# NOTIFYMSG NOCOMM "UPS %s is unavailable"
# NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"
#
# Note that %s is replaced with the identifier of the UPS in question.
#
# Possible values for <notify type>:
#
# ONLINE : UPS is back online
# ONBATT : UPS is on battery
# LOWBATT : UPS has a low battery (if also on battery, it's "critical")
# FSD : UPS is being shutdown by the master (FSD = "Forced Shutdown")
# COMMOK : Communications established with the UPS
# COMMBAD : Communications lost to the UPS
# SHUTDOWN : The system is being shutdown
# REPLBATT : The UPS battery is bad and needs to be replaced
# NOCOMM : A UPS is unavailable (can't be contacted for monitoring)
# NOPARENT : The process that shuts down the system has died (shutdown impossible)

# --------------------------------------------------------------------------
# NOTIFYFLAG - change behavior of upsmon when NOTIFY events occur
#
# By default, upsmon sends walls (global messages to all logged in users)
# and writes to the syslog when things happen. You can change this.
#
# NOTIFYFLAG <notify type> <flag>[+<flag>][+<flag>] ...
#
# NOTIFYFLAG ONLINE SYSLOG+WALL
# NOTIFYFLAG ONBATT SYSLOG+WALL
# NOTIFYFLAG LOWBATT SYSLOG+WALL
# NOTIFYFLAG FSD SYSLOG+WALL
# NOTIFYFLAG COMMOK SYSLOG+WALL
# NOTIFYFLAG COMMBAD SYSLOG+WALL
# NOTIFYFLAG SHUTDOWN SYSLOG+WALL
# NOTIFYFLAG REPLBATT SYSLOG+WALL
# NOTIFYFLAG NOCOMM SYSLOG+WALL
# NOTIFYFLAG NOPARENT SYSLOG+WALL
#
# Possible values for the flags:
#
# SYSLOG - Write the message in the syslog
# WALL - Write the message to all users on the system
# EXEC - Execute NOTIFYCMD (see above) with the message
# IGNORE - Don't do anything
#
# If you use IGNORE, don't use any other flags on the same line.

# --------------------------------------------------------------------------
# RBWARNTIME - replace battery warning time in seconds
#
# upsmon will normally warn you about a battery that needs to be replaced
# every 43200 seconds, which is 12 hours. It does this by triggering a
# NOTIFY_REPLBATT which is then handled by the usual notify structure
# you've defined above.
#
# If this number is not to your liking, override it here.

RBWARNTIME 43200

# --------------------------------------------------------------------------
# NOCOMMWARNTIME - no communications warning time in seconds
#
# upsmon will let you know through the usual notify system if it can't
# talk to any of the UPS entries that are defined in this file. It will
# trigger a NOTIFY_NOCOMM by default every 300 seconds unless you
# change the interval with this directive.

NOCOMMWARNTIME 300

# --------------------------------------------------------------------------
# FINALDELAY - last sleep interval before shutting down the system
#
# On a master, upsmon will wait this long after sending the NOTIFY_SHUTDOWN
# before executing your SHUTDOWNCMD. If you need to do something in between
# those events, increase this number. Remember, at this point your UPS is
# almost depleted, so don't make this too high.
#
# Alternatively, you can set this very low so you don't wait around when
# it's time to shut down. Some UPSes don't give much warning for low
# battery and will require a value of 0 here for a safe shutdown.
#
# Note: If FINALDELAY on the slave is greater than HOSTSYNC on the master,
# the master will give up waiting for the slave to disconnect.

FINALDELAY




以上の変更後、ホスト(サーバー)を再起動させればUPSがlowbattery時にホスト(サーバー)が
シャットダウンします。また各種異常時等にもシャットダウンします。